Date: January 18, 2002 DSL-BQA Memo
02-001
To: Community Based Residential Facilities CBRF 01
From: La Vern Woodford, Chief, Resident Care Review Section
Via: Susan Schroeder, Director, Bureau of Quality Assurance
Introduction
This is the fifth in a series of BQA Memos that have been sent since
1996 regarding fire protection systems. (Previous memos: DSL-BQA Memo
00-036;
DSL-BQA Memo 99-032;
DSL-BQA Memo 96-044) By January 1, 2002, all Community Based
Residential Facilities (CBRFs) must have an approved, fully
interconnected, or radio-transmitting, fire protection system in all
required locations.
This memorandum outlines fire protection system requirements for CBRFs
that must be in place by January 1, 2002. Because these requirements are
based on Wisconsin
Statutes (exit DHFS), Section 50.035, and on Wisconsin Administrative Code, Section
HFS 83.43 (exit DHFS), no waivers or variances will be provided. CBRFs must be in
compliance with the smoke detection, heat detection, and plan review
submission described below by January 1, 2002. (Please note that the
Chapter HFS 83 code references pertaining to these requirements have been
in effect since November 1996.)
Smoke Detectors
1. Section HFS 83.43(4)(b)1. and 2. All CBRFs shall have at least
one smoke detector in each of the following locations:
-
At the head of every open stairway.
-
On the hallway side of every enclosed
stairway on each floor level.
-
In every corridor, spaced not more than
30 feet apart and not further than 15 feet from any wall or in
accordance with the manufacturer’s separation specifications.
-
In each common use room, including a
living room, dining room, family room, lounge and recreation room, but
not including a kitchen, bathroom or laundry room.
-
In or near the living room of an
apartment.
-
In all bedrooms.
-
In each room of the staff living
quarters, including the staff office, but not including the kitchen or
bathroom.
-
In the basement or in each room in the
basement, except a furnace room or laundry room.
-
In adjoining rooms where the shared
openings have a minimum lintel depth of eight inches from the ceiling.
-
In each compartment of any room if the
openings between compartments have a minimum lintel depth of at least
eight inches from the ceiling.
2. Effective January 1, 1997, facilities were allowed a five-year
extension to comply with the fire alarm system requirements.
3. All CBRFs of nine or more beds are required to have an
interconnected (hard-wired) detection system. CBRFs of eight or fewer beds
are required to have an interconnected or radio-transmitting detection
system per Wisconsin Statute, Section 50.035(2)(a)2.
Note: There is no statutory authority for facilities having nine or
more beds to install a radio-transmitting smoke detection system that is
designed for larger facilities.
Heat Detectors
1) Section HFS 83.43(5)(a). All CBRFs shall have at least one heat
detector integrated with the smoke detection system at all of the
following locations, or in accordance with the heat detector manufacturer’s
separation specifications:
-
The kitchen, when it is a separate
enclosed room, or when it has a shared opening with a minimum lintel
depth of at least eight inches from the ceiling separating it from any
adjoining room.
-
In any attached garage.
-
In the attic or in each enclosed
compartment of the attic.
-
In an enclosed furnace room.
-
In an enclosed laundry room.
2) Section HFS 83.43(5)(b). CBRFs licensed before January 1, 1997,
shall meet the requirements under par. (a) within five years after
January, 1997, or when any smoke detector of the smoke detector system in
the facility on January 1, 1997 needs replacement and new smoke detectors
compatible with the smoke detection system currently in the CBRF are not
available and a new smoke detection system needs to be installed,
whichever comes first.
Interdepartmental Code
Please be advised that the Department of Health and Family Services,
Wisconsin Administrative Code, Section HFS 83.42 and the Department of
Commerce, Commercial Building Code COMM
51.24 [updated to COMM 14], both have requirements concerning fire alarm system design,
construction, inspection, testing, and maintenance referenced in the
National Fire Protection Association (NFPA), Standard 72.
Plan Review
Section HFS 83.56(2). Plan Review. All construction plans for new CBRFs
of any size and any additions to existing buildings shall be reviewed and
approved by the Department before construction.
The Bureau considers the installation of new parts of the fire
protection system to be an addition to the facility.
Any changes to the fire protection system require plan submittal and
approval. For plan review assistance, please call (608) 267-1442 and
reference forms DSL-2333 for CBRFs attached to health care facilities or
DSL-2496 for freestanding CBRFs, or department web site at:
http://www.dhs.state.wi.us/rl_DSL/PlanReview/index.htm
[address updated]
Follow Sections HFS 83.56(2) and (3) for plan review submission and fee
requirements.
Compliance with This Requirement
The department expects all CBRFs to have an approved, fully
interconnected, or radio-transmitting, fire protection system in all
required locations by January 1, 2002. Any facility found not to be in
compliance will be cited and issued a statement of deficiency. In
accordance with Wis. Stat., sec. 50.03(5g)(c)1, a daily forfeiture
will be assessed from January 1, 2002, until the facility is in
compliance. Forfeitures will range from $10 per day (facilities
that are making good faith efforts to get into compliance) to $50 per
day (facilities that have not done anything to get into compliance).
If you have questions, please contact the appropriate Regional Field
Operations Director listed below [via Regional
Offices, ask for Assisted Living Supervisor]