Applicable Codes Relating
to Fire Protection Systems to Meet the January 1, 2002 Deadline
PDF Version
of BQA 00-036 (PDF, 10 KB)
Introduction | Rules_&_Regulations
| Forms | Providers | Contacts | What's_Happening |
Publications | Related Sites
Date: May 1, 2000 DSL-BQA Memo 00-036
To: Community Based Residential Facilities CBRF 15
From: La Vern Woodford, Chief, Resident Care Review Section
via: Susan Schroeder, Director, Bureau of Quality Assurance
Introduction
By January 1, 2002, all Community Based Residential Facilities
(CBRFs) must have an approved fully interconnected or radio-transmitting fire protection
system in all required locations.
This memorandum outlines fire protection system requirements for CBRFs that must be in
place by January 1, 2002. Because these requirements are based on Wisconsin Statutes,
Section 50.035, and to Wisconsin Administrative Code, Section HFS 83.43, no waivers or
variances will be provided. CBRFs must be in compliance with the smoke detection, heat
detection, and plan review submission described below by January 1, 2002. (Please note
that the Chapter HFS 83 code references pertaining to these requirements have been in
effect since November 1996.)
Smoke Detectors
1. Section HFS 83.43(4)(b)1. and 2. All CBRFs shall have at least
one smoke detector in each of the following locations:
-
At the head of every open stairway.
-
On the hallway side of every enclosed stairway on each floor level.
-
In every corridor, spaced not more than 30 feet apart and not further than 15 feet from
any wall or in accordance with the manufacturers separation specifications.
-
In each common use room, including a living room, dining room, family room, lounge and
recreation room, but not including a kitchen, bathroom or laundry room.
-
In or near the living room of an apartment.
-
In all bedrooms.
-
In each room of the staff living quarters, including the staff office, but not including
the kitchen or bathroom.
-
In the basement or in each room in the basement, except a furnace room or laundry room.
-
In adjoining rooms where the shared openings have a minimum lintel depth of eight inches
from the ceiling.
-
In each compartment of any room if the openings between compartments have a minimum
lintel depth of at least eight inches from the ceiling.
2. Effective January 1, 1997, facilities were allowed a five-year extension
to comply with the fire alarm system requirements.
3. All CBRFs of nine or more beds are required to have an interconnected
(hard-wired) detection system. CBRFs of eight or fewer beds are required to have an
interconnected or radio-transmitting detection system per Wisconsin Statute, Section
50.035(2)(a)2.
Note: There is no statutory authority for facilities having nine or more beds to
install a radio-transmitting smoke detection system that is designed for larger
facilities.
Heat Detectors
1. Section HFS 83.43(5)(a). All CBRFs shall have at least one heat
detector integrated with the smoke detection system at all of the following locations, or
in accordance with the heat detector manufacturers separation specifications:
-
The kitchen, when it is a separate enclosed room, or when it has a shared opening with a
minimum lintel depth of at least eight inches from the ceiling separating it from any
adjoining room.
-
In any attached garage.
-
In the attic or in each enclosed compartment of the attic.
-
In an enclosed furnace room.
-
In an enclosed laundry room.
2. Section HFS 83.43(5)(b). CBRFs licensed before January 1, 1997, shall meet the
requirements under par. (a) within five years after January, 1997, or when any smoke
detector of the smoke detector system in the facility on January 1, 1997 needs replacement
and new smoke detectors compatible with the smoke detection system currently in the CBRF
are not available and a new smoke detection system needs to be installed, whichever comes
first.
Interdepartmental Code
Please be advised that the Department of Health and Family Services,
Wisconsin Administrative Code, Section HFS 83.42 and the Department of Commerce,
Commercial Building Code COMM 51.24, both have requirements concerning fire alarm system
design, construction, inspection, testing, and maintenance referenced in the National Fire
Protection Association (NFPA), Standard 72.
Plan Review
Section HFS 83.56(2). Plan Review. All construction plans for new CBRFs
of any size and any additions to existing buildings shall be reviewed and approved by the
Department before construction.
The Bureau considers the installation of new parts of the fire protection system to
be an addition to the facility.
Any changes to the fire protection system require plan submittal and approval. For plan
review assistance, please call (608) 267-1442 and reference forms DSL-2333 for CBRFs
attached to health care facilities or DSL-2496 for freestanding CBRFs.
Follow Sections HFS 83.56(2) and (3) for plan review submission and fee requirements.
You may wish to initiate your plan review submission soon in order to meet the January 1,
2002 deadline for an installed and approved system.
Fire Reporting
Facilities are required to report a fire to the Department within three
working days after a fire event occurs on the premises of a CBRF per Section HFS
83.19(3)(a). Facilities can report using various means:
-
Form DSL-2500
(PDF, 23 KB) entitled "Fire Report"
-
Copy of Fire Department report
-
Facility letterhead describing the event with the administrators signature
included
Summary
By January 1, 2002, all CBRFs must have an approved, fully
interconnected or radio-transmitting fire protection system in all required locations.
If you have questions, please contact the appropriate Regional Field Operations
Director listed below [via Regional
Offices, ask for Assisted Living Supervisor]
PDF: The free Acrobat Reader®
software is needed to view and print portable document format (PDF) files. Learn
more.
|